Conductor: Tinned annealed flexible copper-Class 5 according to EN 60228
Insulation: Halogen free Cross-linked compound, “Type EI 5” according to EN 50363-5
Colour: Green/Yellow, Black and all other colors are available upon request
Rated Voltage (U0/U)
AC 450 / 750 V
Test Voltage
AC 2,5 kV
Operating Temperature
-40°C / +90°C
Insulation Temperature
-5°C / +60°C
Short Circuit Temperature
+250°C (Max. 5 sec.)
Min. Bending Radius
(As per EN50525-1 Table.3)
4 x D for cable D ≤ 8 mm
5 x D for cable 8 mm < D ≤ 12 mm
6 x D for cable D > 12 mm
Electrical Test
EN 50395
Non-electrical Tests
EN 50396
Insulation Resistance
EN 50525-3-41 Table B.2
Ozone Resistance
IEC 60811-403, EN 50396 Clause 8.1.2
UV Resistance
IEC 62930:2017 (Annex E), EN 50618 (Annex E)
Halogen Free Properties
EN 50525-1 (Annex B), IEC 60764-1, EN 50363-5
Low Smoke Emission
EN 61034-1 / 2 (Light transmittance > 80%)
Flame Retardancy
EN 60332-1-2
Number Of Cores |
Cross Sections mm2 |
Conductor Diameter mm |
Overall Diameter mm |
Bending Radius (min.) mm |
Weight kg/km |
1 |
1,5 |
1,6 |
3,10 -0,2 /+0,3 |
12,4 |
20 |
1 |
2,5 |
2,0 |
3,70 -0,2 /+0,3 |
14,8 |
31 |
1 |
4 |
2,5 |
4,20 -0,2 /+0,3 |
16,8 |
45 |
1 |
6 |
3,0 |
4,50 -0,2 /+0,3 |
18,0 |
61 |
1 |
10 |
4,0 |
5,90 -0,2 /+0,3 |
23,6 |
103 |
1 |
16 |
5,0 |
6,90 -0,2 /+0,3 |
27,6 |
155 |
1 |
25 |
6,1 |
8,50 -0,3 /+0,5 |
42,5 |
238 |
1 |
35 |
7,4 |
10,00 -0,3 /+0,5 |
37,0 |
335 |
1 |
50 |
8,8 |
11,90 -0,3 /+0,5 |
59,5 |
480 |
1 |
70 |
10,5 |
13,70 -0,3 /+0,5 |
82,2 |
674 |
1 |
95 |
11,9 |
15,40 -0,3 /+0,5 |
92,4 |
871 |
REACH and RoHS Complaint
CE conformity
UV & Ozone Resistant
General requirements acc. to EN 50525-1
Guide to use acc. to EN 50565-1